For on / off P + I control of valves, fan and auxiliary power supply systems. Available for 2 or 4 pipe system.
Heating / cooling control with auxiliary power supply system (required for sensor agent);
- Control electric heating / cooling source;
- Only ventilation;
- Automatic adjustment (required for sensor agent or external contact);
- Antifreeze protection (if the glass contact is activated);
Temperature adjustment range |
10 ... 30 oC; |
Input signal |
Optional ambient temperature sensor, contact pipe contact, contact energy saving in case of damage, glass contact and automatic adjustment; |
Command outputs |
triac (230V 0,8A) on/off or PWM for heating and cooling valve, switches (230V 1,25A up to 3A) for fans (3-speeds) and auxiliary source; |
Feeding |
230 Vac | 5 VA; |
|
Ambient temperature control; fan speed auto/off/low/med/high; |
Case (LxLxA) |
88 mm | 118 mm | 31 mm; |
Protection class |
IP30; |
Mounting |
Directly on the wall, wall, ventiloconvector housing; |
Maximum section cable |
2,5 mm2; |
Documentation language |
Thermostat supplied with instructions for use in English, French, Italian and Spanish. |
Description |
Cod |
Ambient temperature sensor NTC10k. |
RFCA-SR10 |